In-Rack Liquid-to-Air CDU Selection Guide

Compare 4 models from 6 to 30 kW and match the equipment to your cooling loop.

In-Rack Liquid-to-Air CDU
In-Rack Liquid-to-Air CDU — series illustration; dimensions vary by model.
APPLICATION ENGINEERING

Edge rooms & pilot racks

Room HVAC removes heatIT loadRack-mounted CDURoom airConceptual application layout · configuration and sizing depend on the project

How it is used

Add direct-to-chip cooling where facility water is unavailable. The room cooling system must remove the heat rejected by the CDU.

Selection checkpoint

Confirm inlet air temperature, rack space and room heat-rejection capacity.

Illustrative architecture, not a customer installation or an installation drawing.

Where this equipment fits

For enterprise / edge rooms without facility water, university and finance clusters, single-rack GPU pilots: only power and room air conditioning are needed to run direct-to-chip liquid cooling — no chilled water or cooling tower. 35 °C secondary supply is obtained from 25 °C room inlet air (10 °C approach); capacity derates with warmer room air per the selection table. Pairs with ToneCooling cold plates, manifolds and hose assemblies from the same factory.

Compare the model range

ModelCapacityRated flowSize / heightEnglish datasheet
TC-CDU-A6R6 kW10 L/min6U↓ Download PDF
TC-CDU-A15R15 kW25 L/min10U↓ Download PDF
TC-CDU-A24R24 kW40 L/min15U↓ Download PDF
TC-CDU-A30R30 kW50 L/min20U↓ Download PDF

Selection workflow

  1. Establish the design heat load and the required redundancy or future capacity margin.
  2. Confirm the source and sink temperatures. Liquid-to-air capacity depends on room inlet air; liquid-to-liquid capacity depends on facility water and approach temperature.
  3. Calculate required coolant flow using the actual fluid properties and temperature rise.
  4. Check the pump curve against the complete loop pressure drop, including cold plates, manifolds, hoses, filters and connections.
  5. Confirm mounting space, maintenance access, electrical supply, connections, controls and site conditions.
  6. Agree the acceptance test, drawings, communication register map and commissioning scope before ordering.

Flow and thermal sizing

Q = 60,000 × P / (ρ × cp × ΔT), where Q is L/min, P is kW, ρ is kg/m³, cp is kJ/(kg·K), and ΔT is K. Use fluid properties at the design temperature. Thermal flow alone does not establish available pump head or guaranteed system capacity.

Note: rated at 25 °C inlet air, 35 °C secondary supply, PG25; derate per selection table for other inlet air temperatures. Platform names indicate compatibility only and imply no endorsement or partnership. Specifications subject to change.

Installation and service checks

  • Maintain access for pump, filter and heat-exchanger service.
  • Confirm all wetted materials and seals are compatible with the specified coolant.
  • Agree flushing, filling, venting, leak testing and alarm verification procedures.
  • Validate BMS / DCIM communication and automatic switchover under the agreed test conditions.

Documentation to request

Supplied: dimensional / connection drawing, P&ID, Modbus register map, flow–pressure-drop curve, selection table, user manual. Factory tests: pressure hold, leak test, flow resistance at rated flow, pump / ATS switchover, leak-sensor / coolant-quality / comms check; records ship with every unit. Combined cold plate + manifold + CDU report for full-rack projects.

Liquid Cooling Without Facility Water: Common Questions

Can you run direct-to-chip liquid cooling without facility water?

Yes. An in-rack liquid-to-air CDU circulates coolant to the cold plates and rejects the heat to room air through its built-in heat exchanger and fans, so only power and room air conditioning are needed — no chilled water or cooling tower. ToneCooling’s in-rack liquid-to-air range covers 6 to 30 kW per unit.

What does the room need to handle?

The room cooling system must remove the heat the CDU rejects. Confirm room inlet air temperature, rack space and room heat-rejection capacity before ordering; capacity derates with warmer room air per the selection table.

Which model fits one GPU rack?

Match the model to the rack’s design heat load: TC-CDU-A6R 6 kW (6U), TC-CDU-A15R 15 kW (10U), TC-CDU-A24R 24 kW (15U) or TC-CDU-A30R 30 kW (20U). For several racks in an air-cooled room, see the in-row liquid-to-air CDU guide (60–600 kW).

Get a CDU selection review

Send your rack or loop heat load, inlet temperature, coolant, required flow, pressure drop, power supply and available space. We will confirm the model and operating conditions.

Request an engineering review