H100 vs H200 Liquid Cooling: Cold Plate Datasheet Comparison

Last updated: November 9, 2026 · ToneCooling Engineering Team

H100 vs H200 liquid cooling: both ToneCooling sets cool an 8-GPU board with four NVSwitch cold plates, but the H100 assembly (T-HS202323) is rated 6.344 kW at 9 L/min and a 45 °C inlet, while the H200 set (TC-BZP-H200-01A) is rated 8 × 700 W + 2 × 134 W + 2 × 156 W at 8.0 L/min and a 38 °C inlet. GPU heat load is the same 700 W per GPU on both datasheets; the loop conditions are not. This page compares the two datasheets so you can size the coolant loop and order the right set.

Request RFQH100 datasheet (PDF)H200 datasheet (PDF)

What Is the Difference Between H100 and H200 Liquid Cooling?

The main difference is the operating point each set is rated for, not the GPU heat load. Both datasheets list 700 W per GPU across eight GPUs. The H100 assembly is rated with a 45 °C pure-water inlet at 9 L/min and allows up to 40 kPa pressure drop; the H200 set is rated with a 38 °C inlet at 8.0 L/min and 18.5 kPa (±20%). The NVSwitch load is also split differently: 4 × 186 W on the H100 assembly, and 2 × 134 W + 2 × 156 W on the H200 set.

Both are standard ToneCooling products supplied to a published datasheet and made in our own manufacturing facility in Huizhou, China. ToneCooling is an independent manufacturer; both sets are H100 / H200 platform-compatible designs.

ToneCooling H100 liquid cooling assembly with eight GPU cold plates, NVSwitch cold plates, manifolds and hose assemblies
H100 GPU + NVSwitch liquid cooling assembly (T-HS202323): eight GPU cold plates, four NVSwitch cold plates, hoses and quick disconnects.

H100 vs H200 Cold Plate Specifications

ItemH100 assembly (T-HS202323)H200 set (TC-BZP-H200-01A, Rev B)
Board8 × H100 GPU + 4 × NVSwitchH200 (SXM5) 8-GPU + NVSwitch
Rated heat load (W)700 W × 8 + 186 W × 4 = 6,344 W8 × 700 W + 2 × 134 W + 2 × 156 W = 6,180 W
CoolantPure waterPure water
Inlet temperature (°C)4538
Flow rate (L/min)9 (rated system flow)8.0 (feed flow)
Pressure drop (kPa)40 maximum at 9 L/min18.5 (±20%)
Max operating pressure (MPa)10.8
Temperature limitMaximum component temperature below 80 °CCold plate surface below 65 °C
Size (mm)472.7 × 331 × 130.6 (full assembly)GPU plate 151 × 78.2 × 43.14; switch plate 80 × 64.3 × 7.6
MaterialCopperT2 copper
ConnectionsIntegrated flexible hoses and color-coded quick disconnectsQuick disconnects, per project

Source: ToneCooling datasheets T-HS202323 (Rev 1.0) and TC-BZP-H200-01A (Rev B). Totals are the sum of the listed loads. The two sets are rated at different inlet temperatures and flows, so compare each one with your own loop conditions rather than with each other.

How Much Coolant Flow Does an H100 or H200 Board Need?

Design for the rated flow on the datasheet: 9 L/min per H100 assembly and 8.0 L/min per H200 set. At those flows the coolant temperature rise across one board is roughly 10 °C for H100 and 11 °C for H200 at full rated load. These are our calculations from the datasheet heat load and flow, using the heat capacity of water (about 4.19 kJ/kg·K); they are not measured values.

Per 8-GPU board (calculated)H100 (T-HS202323)H200 (TC-BZP-H200-01A)
Heat to coolant (kW)6.3446.18
Rated flow (L/min)98.0
Approx. coolant temperature rise (°C)about 10about 11
Approx. outlet at rated inlet (°C)about 55 (45 inlet)about 49 (38 inlet)

To size a CDU, multiply the board flow by the number of boards on the loop and add margin for manifolds, hoses and quick disconnects. For example, four H200 boards need about 32 L/min of feed flow at a 38 °C supply. ToneCooling also supplies coolant distribution units (CDUs) from 6 kW to 2 MW, so cold plates and CDU can be quoted as one package, or the sets can work with the CDU you have already selected.

When Should You Choose the H100 Assembly or the H200 Set?

Choose by the board you are building and the facility water you have, not by the higher number.

Choose the H100 assembly (T-HS202323) when

  • You are cooling an 8-GPU H100 board with four NVSwitch chips.
  • Your loop supplies warm water up to a 45 °C inlet at 9 L/min, and your pump can cover up to 40 kPa per board.
  • You want one complete assembly with plates, hoses and color-coded quick disconnects, and a 1 MPa pressure rating.

Choose the H200 set (TC-BZP-H200-01A) when

  • You are cooling an H200 (SXM5) 8-GPU + NVSwitch board.
  • Your loop supplies 38 °C water at 8.0 L/min and you want a lower pressure drop of 18.5 kPa (±20%) per board.
  • You need the GPU plate envelope of 151 × 78.2 × 43.14 mm and a 0.8 MPa pressure rating.

Not sure which applies? Send the board drawing or STEP file with your RFQ and an engineer will confirm the matching set.

ToneCooling H200 cold plate set with eight GPU cold plates, NVSwitch cold plates, two manifolds and color-coded quick disconnects
H200 GPU + NVSwitch liquid cold plate set (TC-BZP-H200-01A, Rev B).

How Are H100 and H200 Cold Plates Tested?

Every H100 assembly and H200 set goes through 100% helium leak testing, with acceptance criteria set per project. Thermal resistance, leak and flatness test reports are available on request, and both datasheets download without a form. H200 thermal resistance is validated per project by CFD. Our quality system is IATF 16949-aligned.

ToneCooling technician leak testing a liquid cold plate at a test bench with a pressure leak tester
Leak testing a liquid cold plate before shipment.

What Should an H100 or H200 Cold Plate RFQ Include?

  • Board and part number: H100 (T-HS202323) or H200 (TC-BZP-H200-01A).
  • Quantity and project stage (evaluation, pilot or production).
  • Coolant, supply temperature, available flow per board and allowed pressure drop.
  • Fitting type and port position, with a STEP or PDF of the tray if position matters.
  • Test documents you need: helium leak, thermal resistance, flatness.

Custom samples are available from a single piece. An engineer reviews every RFQ and replies by email with next steps.

Request RFQ

Need the STEP model or a test report first? Choose the product and the document below.

STEP Model & Test Report Request

H100 vs H200 Liquid Cooling FAQ

Does the H200 need more cooling than the H100?

Not per GPU on our datasheets: both list 700 W per GPU. The H200 set is rated 6,180 W per board in total and the H100 assembly 6,344 W, because the NVSwitch loads differ. The bigger difference is the loop: 38 °C at 8.0 L/min for H200 versus 45 °C at 9 L/min for H100.

Can I use H100 cold plates on an H200 board?

Order the set that matches your board. The H100 assembly and the H200 set are separate standard products, each qualified to its own datasheet, with different switch plate loads, pressure drop and pressure rating. If you plan to move an existing H100 loop to H200 boards, send the board drawing and we confirm the fit at quotation.

Which needs more coolant flow, H100 or H200?

The H100 assembly is rated at 9 L/min per board and the H200 set at 8.0 L/min. The H100 assembly allows up to 40 kPa pressure drop at 9 L/min, while the H200 set is rated 18.5 kPa (±20%), so check your pump curve against the board you use.

Do H100 and H200 servers need liquid cooling?

Both GPUs are sold in air-cooled and liquid-cooled servers. Direct-to-chip cold plates are used when rack density, fan power or facility limits make air cooling hard to run. With about 6.2 to 6.3 kW per 8-GPU board going into water, a liquid loop removes most of the board heat without moving that heat into room air.

Are the H100 and H200 cold plates standard products?

Yes. Both are ToneCooling standard products supplied to published datasheets: T-HS202323 for H100 and TC-BZP-H200-01A Rev B for H200. Fittings and port positions can be set per drawing, and other GPU platforms are built as custom cold plates.

See the full H100 8-GPU liquid cooling assembly and H200 cold plate set pages, compare the newer GB300 vs GB200 cold plates, read the GB200 NVL72 cooling requirements, or browse all liquid cold plates, including custom designs. Platform background: NVIDIA H100 and NVIDIA H200.

NVIDIA, H100 and H200 are trademarks of NVIDIA Corporation; no affiliation or endorsement is implied.

Scroll to Top

Get A Free Quote Now !

If you have any questions, please do not hesitate to contact us.

Quote Request
ToneCooling 19 thermal management